About Enclosures

4x2 Enclosure

The CBNA Enclosures are design to house CBNA DMX drivers and CBNA Processors in a clean and safe manner.

Front vented panel provides heat dissipation.

16- gauge cold rolled steel.

4x1 Schematic4x2 Schematic

Dimensions & Weight

EnclosureDimensions(Imperial)Dimensions (Metric)Weight (lbs)Weight (kg)
4x264” x 30-3/8” x 4-1/16”162.56 x 78.23 x 10.16 cm75.00 lbs34.00 kg
4x164” x 15-3/8” x 4-1/16”162.56 x 39.12 x 10.16 cm43.00 lbs19.50 kg
2x136” x 15-3/8” x 4-1/16”91.44 x 39.12 x 10.16 cm25.00 lbs11.36 kg

Maximum Weight Capacity

EnclosureMaximum Weight
4x2200 lbs
4x1100 lbs
2x150 lbs

Accessories Included

Quantities4X24X12x1
15A duplex outlet060303
Steel junction box060303
Junction box cover060303
Nylon grommet020202
Wire Velcro020201
Bracket lacing020101

Mounting The Enclosure

Enclosures must be solidly installed in dry well vented environment; may be flush mounted or surface mounted.
Surface mounted enclosures should be installed on a ¾’’ plywood reinforced wall. Flush mounted enclosures need to be affixed between stud bays. For best results, 5/8in. (16mm) drywall is preferred.

  • Refer to maximum weight capacity.

  • Consult our website for driver measurements and weight.

  • Enclosures are intended for indoor use only. Dry location only.

  • Enclosures house equipment that requires to be air-cooled, mount in a well-ventilated area.

  • The ambient temperature range is 32°F to 104°F (0°C to 40°).

  • The relative humidity range is 10% to 90% (non-condensing).

  • Allow adequate clearance in front of the vented cover for servicing and ventilation.

surface and flush mounted

Electrical Distribution

WARNING

ALL POWER FEEDS MUST BE PROTECTED BY A DEDICATED 20 AMP CIRCUIT BREAKERS, SUPPLIED AND INSTALLED BY CERTIFIED ELECTRICIANS IN ACCORDANCE TO LOCAL AND NATIONAL ELECTRICAL CODES.

  • Enclosure must be wired by a certified low voltage installer in accordance with all local codes.

  • Enclosure should be grounded as per local and national electrical codes.

  • Never load electrical breakers at more then 80% capacity.

  • Calculate AC amperage consumption to determine appropriate electrical requirements and electrical distribution in each enclosures.

  • Use 12/2 cable for external electrical distribution.

  • Use copper conductors only – rated at 60°C.

  • Low voltage and AC should be run within the enclosure separately.

  • If more then one circuit is necessary in a same enclosure, use same electrical phase.

Electrical lateral connection15A outlet parts

Equipment power consumption

Power Supply Usage @ 80%

WATTSDC AMPAC AMP
HLG-320-24 13.4A240101.81
HLG-240-24 10A19281.45
HLG-100-24 4A963.20.6
CBNA-200-Z4NA1050 mA1.55

Wire Placement

Component Configuration

  • Refer to our website for specifications regarding maximum weight capacity.

  • Keep AC separated from low voltage using our included bracket lacing.

  • Use provided nylon grommets to protect any wires from damage at top and bottom of enclosure.

  • Leave space between drivers for aeration purpose.

Enclosure with components

CBNA offers in-factory system configuration and / or assembly should alternate UL certified configurations be required.

Contact CBNA for applicable fees.

Last Updated: 8/13/2018, 3:56:46 AM